MBS UNIQUE PLUG IN TRANSDUCER OPTION (general information)

Product

group

W

NMC

Features

  • Unique plug in transducer modules
  • 0-10VDC output
  • 0-20mA output
  • 4-20mA output
  • Powered and non powered versions
  • Secondary of the CT repeated
Download data sheet

Do you ultimately need an analogue signal for your current measurement? The MBS range of CT’s feature a plug in transducer module option.

Just twist off the secondary terminal covers and remove the secondary terminal screws. Screw in the brass transformer to module connecting studs and plug in the NMC transducer module.

Each NMC transducer block will give two different isolated analogue outputs. Also the secondary of the current transformer is repeated, if this repeat facility is not required the supplied shorting link must be left in situ. It is possible to generate 0-20mA and 0-10VDC without any auxiliary supply (self powered module version). Please note that the self powered versions can only be used on current transformers with an output of at least 2.5VA, if a 4-20mA signal is required in all cases an auxiliary supply is required, 24VDC, 110VAC or 230VAC.

1. Remove red CT secondary covers by twisting them, some gentle force is required.

2. Remove the secondary screws on the P2 (L) side of the CT, pull out the brass studs from the rear of the transducer / relay module and screw into the holes left by the secondary screws.

3. Clip transducer module on to the top of the CT.

4. If the 1Amp / 5Amp CT output is not required the link for shorting should be left in situ across terminals 5 & 6.

1. On connection of the auxiliary supply the two green LED’s should illuminate.

2. Note, the self powered transducer version is only possible to use if the CT being used generates at least 2.5VA. The self powered version current output is 0-20mA instead of 4-20mA.

Terminal No. Designation

1 Negative 0-10VDC output
2 Positive 0-10VDC output
3 Negative 0-20mA / 4-20mA output *
4 Positive 0-20mA /4-20mA output *
5 S1 (k) 1Amp /5Amp output *
6 S2 (I) 1Amp / 5Amp output *
7
+ / L auxiliary supply *
8 - / N auxiliary supply *

* Depending on version ordered

NMC-Connections.png#asset:3847


INPUT

Current: 1Amp or 5Amp

Power consumption:
<1VA
Self powered versions >2.5VA

Overload capacity:
1.2x In continuously
8x In <40secs

OUTPUT

Signal I: 0-20mA or 4-20mA

Max external resistance: 500 ohms

Current limit on overload: <34mA

Signal V: 0-10VDC

External resistance: >10 Kohms

Voltage limit on overload: 18VDC

GENERAL

DC auxiliary supply: 24VDC ± 15%

AC auxiliary supply: 110VAC, 230VAC ± 10%, 50-60Hz

Response time: <500 mSec

General accuracy: Class 0.5

Accuracy range:
1-120% In powered
15-120% self powered

Isolation: 4KV