AC "CT" STYLE CURRENT TRANSDUCERS

Product

group

X

CS-6 (Solid core), SC-6 (Split core)

Features

  • "CT" style
  • Moulded case insulation to 600VAC
  • Solid core & split core versions
  • Din rail mounted
  • Self powered 0-5VDC & 0-10VDC outputs
  • Loop powered 4-20mA output
  • Primary currents from 0-2 Amps to 0-200 Amps
  • Units for TRMS measurement, 20-400Hz frequency range
Download data sheet

The CS-6xx & SC-6xx range of AC current transducers look like standard current transformers and are used as such. The range is available in standard ring type, or for retro fit projects in split core. Either way both types are Din rail mountable, moulded case and insulated up to 600VAC.

Some of the transducers are dedicated primary ranges, whilst others have selectable primary ranges, selectable via a slider switch or jumpers, like traditional CT’s primary turns can be made to reduce the ratio. Three output options are available, either a 0-5VDC or 0-10VDC output which is self powered. The 4-20mA version is a loop powered output and therefore requires a nominal 24VDC external source to power the loop.

The 675 types are designed to measure complex and distorted wave forms being a TRMS device, they are also ideal for current measurement on the output side of VFD’s, as they have a frequency range of 20-400Hz.

Response Time:
Types 650 & 651 (200mSec)
Types 652 (250mSec)
Types 675 (500mSec)

Accuracy:
Class 2
Class 1 on request

0-5VDC Output:
Self powered
Load 1 MOhm typical

0-10VDC Output:
Self powered
Load 1 MOhm typical

4-20mA Output:
15-30VDC loop powered
Max load 600 Ohms (@24VDC)

Temp Range: -15°C to +60°C

Types 675: (-15°C to +50°C)

Humidity: 5-90% RH

CS Dimensions:
Aperture 20.3mm Dia.
Body 66W x 67H x 25mmD

SC Dimensions:
Aperture 20.3mm Dia.
Body 67W x 69H x 24mmD

Enclosure: ABS/PC, UL94V-0

Approvals: cULus listed

CE Marked: Yes

CS-6xxx-Ordering-info.png#asset:3846

CS = Solid Core
SC = Split Core

* Range switch selectable
** Range jumper selectable
*** On the split core variant the max continuous current is x3 of the range selected
**** On the split core variant the max continuous current is x2 of the range selected
***** On the split core variant the max continuous current is 300Amps