DIN 96mm THREE LINE DISPLAY, 3 METERS IN 1, MULTI DISPLAY ENERGY METER

Product

group

EE

CUBE 950

Features

  • Panel mounting
  • Suitable for 1ph or 3ph loads, 3 wire or 4 wire
  • Meters 3 x 3ph loads or 9 x 1ph loads, or in any combination
  • TRMS measurement to 80th Harmonic
  • 4 x isolated configurable pulse or alarm outputs
  • Optional MODBUS RTU output
  • Optional MBus output
  • Current input via 333mVAC split core CT's
  • Class 0.5 accuracy
Download data sheet

The MULTICUBE 950 is a Din 96mm three line display, powerful and extremely cost effective “3 in 1” metering solution, monitoring 3 x 3 phase loads (3 wire or 4 wire) or, 9 x 1 phase loads or a combination of them, for example 2 x 3 phase loads and 3 x 1 phase loads.

Cost effectiveness per meter point is further enhanced by just one voltage and comms connection per MULTICUBE 950. Further time savings come from the “Plug & Play” RJ12 to RJ12 CT adaptors, included as part of the kit. Each three 333mV secondary CT kits are supplied with their secondary tails already terminated into the adaptor and the RJ12 cables do the rest. In the case of single phase loads three loads go to one adaptor.

The MULTICUBE 950 also features innovative “Auto CT Recognition”, this avoids errors from programming the CT primaries incorrectly by automatically recognising the CT primaries for you. Additionally, “Auto CT Rotation” compensates for CT’s installed the wrong way round. Plus “Auto CT Accuracy Compensation” guarantees the accuracy of your data, the meter will compensate for any phase angle errors in your CT’s, giving peace of mind that data will not contain any hidden inaccuracies.

Further safeguards against error are provided by the RJ12 plugs that cannot be installed the wrong way round. This just leaves the possibility of installing the CT’s on the wrong phases (CT’s not in phase). Should this occur a warning on the meter’s large backlit display comes up informing there is an error.

The very powerful MULTICUBE 950 also packs in demands and alarms as standard and fast communication options allow up to 20 reads every second. The fast MODBUS RTU option also provides aggregated “3 in 1” data and optional 100mSec reading updates. Also included is a MODBUS test facility to test the integrity of the MODBUS wiring.

The MULICUBE 950 auto scales to Wh, KWh, MWh etc, depending on the CT ratio programmed. The MULTICUBE 950 is able to accept a very wide voltage input span of 80-480V L-L or 46-277V L-N, thus enabling the CUBE 400 to be used on VT circuits such as 11KV/110V, therefore a VT ratio can also be programmed if required.

Inputs

System:
1 phase,
3 phase, 3 wire or 4 wire balanced or unbalanced

Voltage: 80-480V L-L / 46-277V L-N +20%

Current:
Via external 333mV split core CT’s

Frequency: 45-65Hz

Harmonics:
Input to 80th Harmonic
Individual measured to 63rd (option)

Voltage burden: < 0.1VA per phase

Current burden: < 0.1VA per phase

Voltage overload: x4 for 1 hour

Current overload: x40 for 0.5 Sec max

Auxiliary supply:
230VAC 50/60Hz +15%
On request 110VAC
On request 24VDC

Load:
4VA max
4W max

General

Temperature: Operating -10 ̊C to +55 ̊C

Humidity: <75% non condensing

Material: Mablex to UL94-V-0, self ext.

Terminals: 4mm rising cage

Dimensions: 96x96x83.5mm (72mm behind panel)

KWh:
Class 1 per EN 62053-21
Class 0.5 per ANSI C12.20

KVArh: Class 2 per EN 62053-23

KW & KVA: Class 0.25 IEC 60688

KVAr: Class 0.5 IEC 60688

Amps & Volts: Class 0.1 IEC 60688

Power Factor: ± 0.2 ̊

Neutral current: Class 0.5 IEC 60688

Pulse output: 1 pulse for KWh, or programmable for an Event Alarm

Scaling: Programmable between 1 & 100 counts of registers

Pulse periods: Programmable between 0.1-20Sec

Type: 4 x NO volt free, optically isolated

Rating: 100mA @ 70VDC/33VAC max

Isolation: 3.5KV for 1 min

Communications modbus RTU

Baud: 4800-38400

Parity: Selectable NONE/ODD/EVEN

ID’s: Joint master & individual meters

Speed: Up to 20 reads per second

Instantaneous: Readings updated every second

Isolation: 3.5KV

Communications MBus

Baud: 1200-9600

ID’s: Joint master & individual meters

Tables: Short / Long configurable

Isolation: 3.5KV

TYPE

MULTICUBE 950
MULTICUBE 950 / MODBUS
MULTICUBE 950 / MODBUS / HARMONICS
MULTICUBE 950 / Mbus
MULTICUBE 950 / Mbus / HARMONICS

OPTIONS*

230VAC aux supply (standard)
110VAC aux supply
24VDC aux supply

333mV SECONDARY CT KITS**

RJ12 to RJ12 CT leads, length 3M
RJ12 to RJ12 CT leads, length 5M
Set of 3 x SCL8 5A with adaptor
Set of 3 x SCL10 30A with adaptor
Set of 3 x SCL16 50A with adaptor
Set of 3 x SCL19 50A with adaptor
Set of 3 x SCL16 100A with adaptor
Set of 3 x SCL19 150A with adaptor
Set of 3 x SCL32 400A with adaptor
Set of 3 x SCL51 800A with adaptor

*Specify
**Please see split core 333mVAC secondary CT’s types: SCL, SCT, ROPE