Product
group
D
Combined phase failure and sequence relays, available in either a din rail or 8/11 pin plug housing. The output is SPCO with an option of DPCO on either the din rail or 11 pin version. Utilising transformer technology the units are available in either 3 or 4 wire versions, the 4 wire version tripping on loss of the Neutral. On power up with all three phases present (plus the Neutral if applicable) and in the correct sequence the output relay will energise, the green and red LEDs also illuminate. On loss of a phase, (or Neutral 4 wire versions), drop in voltage below Umin levels, or incorrect phase sequencing the output relay/s after a fixed time delay of 0.5secs will drop out and the red LED will be extinguished. A green supply on LED only illuminated means that there is a supply to the unit but there is a supply fault or either a combination of; phase loss, under volts or sequence error. All terminal details and information along with the CE mark is clearly marked on the sides of the housing.
Supply & Measuring:
Nominal supply:
3 x 110V AC, 3 x 220V AC, 3 x 380V AC,
3 x 400V AC, 3 x 415V AC, 3 x 440V AC
Tolerance: +15%
System: 3 or 4 wire option
Frequency: 50/60Hz
Nominal Umin (fixed):
80% on all 3 phases
60% on 1 phase drop
Delay on tripping:
0.5sec fixed (wrong sequence)
50mSec (phase loss)
Max power consumption: <3VA
Insulation: 2.5KV 50Hz impulse
Relay outputs:
Output contacts:
SPCO 10Amps/250V AC1
DPCO 8Amps/250V AC1
Mechanical life: 30 Million ops
Electrical life: 200K ops at max rated load
General:
Operating temperature: -20°C to +65°C
Storage temperature: -20°C to +65°C
Max cable size: 4mm
CE marked: Yes
In accordance with:
EN61000-6-1: 2007
EN61000-6-3: 2007
EN61010-1: 2002
Housing material: Polycarbonate, Auto extinguishable to UL 94 V-0
TYPE
YWRP (Din rail SPCO)
8WRP (8 pin SPCO)
11WRP (11 pin SPCO)
YWR2P (Din rail DPCO)
11WR2P (11 pin DPCO)
VOLTAGE
3x110V
3x220V
3x380V
3x400V
3x415V
3x440V*
SPECIAL**
SYSTEM
3W(3 wire)
4W(4 wire)
* 440V only possible as a 3 wire version
OPTION
On 3 wire variants as a no cost option a separate AC auxiliary supply can be specified. This gives the possibility of additional “control circuit” voltage monitoring. If this is lost or is not present, the unit will de-energise or not energise as applicable. 24VAC, 48VAC, 110VAC.
**Available on request special high voltage versions i.e 690V L-L. (Separate auxiliary supply required).