VOLTAGE CONTROL RELAYS, WITH SEPARATE AUXILIARY SUPPLY

Product

group

D

YWRU, 11WRU (spco)

Features

  • Din rail or 11 pin plug in
  • Suitable for both AC & DC voltage control
  • Selectable auto or maual reset
  • Three selectable control ranges from:
  • 0.1 to 400VDC
  • 0.1 to 283VAC
  • Special high voltage versions:
  • 700VDC
  • 1000VDC
  • 1500VDC
  • Dual LED indication
Download data sheet

Voltage control relays suitable for both AC and DC voltage control, available in both din rail and 11 pin plug in. The standard units have three selectable via terminal taps voltage ranges from 0.1 to 400VDC (0.1 to 283VAC). Also available only in the din rail housing are dedicated range “high voltage” control units which are most suitable for “railway traction voltage” monitoring.

“Auto Reset” without latching mode. This mode is determined by EC & B1 or pin 9 & 11 left open. The output relay is energised when the monitored voltage rises above the level selected via the front potentiometer. The output relay will de-energise when the voltage falls back below the level selected less the set hysteresis adjustable 5 to 50% set via a second potentiometer. If the separate auxiliary supply is lost at any time the relay will also de-energise.

“Manual Reset” latching mode. This mode is determined by a wired link between terminals EC & B1 or pins 9 & 11. The output relay energises when the monitored voltage rises above the level selected via the front potentiometer. Once energised the output relay will remain latched even if the monitored voltage falls below the set level less any selected hysteresis. Resetting is achieved by opening the link between terminals EC & B1 or pins 9 & 11 or by removing the auxiliary supply. If whilst resetting the monitored voltage is still above the set level a reset will not be achieved. It is normally preferable in the latching mode to have the adjustable hysteresis set at minimum.

DC Auxiliary Supply Versions

DC auxiliary supply versions are as standard non isolated. For these versions the supply and the measured current must be isolated from each other and must not exceed 50V DC. On request at extra cost isolated versions can be manufactured utilising internally a DC to DC converter.

Supply & Measuring

Nominal supply tolerance: ±15%

Isolation AC versions: Via transformer

Isolation DC versions:
No as standard
Yes via optional internal DC to DC converter

Power consumption: 3VA max

Hysteresis: Adjustable 5 to 50% of Ue

Repeat accuracy:
±2% at constant ambient
±5% across temperature range

Response time:
100 mSec on make
200 mSec on break

Relay outputs:

Output contacts: SPCO 10Amps/250V AC1

Mechanical life: 30 Million ops

Electrical life: 200K ops at max rated load

General:

Operating temperature: -20°C to +65°C

Storage temperature: -20°C to +65°C

Max cable size: 4mm

CE marked: Yes

In accordance with:
EN61000-6-1: 2007
EN61000-6-3: 2007
EN61010-1: 2002

Housing material: Polycarbonate, Auto extinguishable to UL 94 V-0

Input ranges parameters:

YWRU-Table.png#asset:3399


TYPE

YWRU (Din rail)
11WRU (11 pin plug in)
YWRU/700V (Din rail)
YWRU/1000V (Din rail)
YWRU/1500V (Din rail)

COIL VOLTAGE

440VAC
415VAC
400VAC
380VAC
230VAC
110VAC
48VAC
24VAC
*48VDC
*24VDC

* No isolation on DC versions as standard, on request at extra cost isolated versions are available.

YWRU-Connections.png#asset:3397

Dimensions-YW-8W11W.png#asset:3263

YWRU-Function.png#asset:3398

Recently Viewed Products

Keep Updated

Receive updates about our offers, latests products and more, directly to your inbox