DIN 96mm SINGLE LINE DISPLAY, MULTI DISPLAY ENERGY METER

Product

group

EE

CUBE 350

Features

  • Panel mounting
  • Suitable for 3 phase loads 3 wire or 4 wire
  • Suitable for single phase loads
  • TRMS measurement to 30th Harmonic
  • Isolated pulse output as standard
  • Optional MODBUS RS485 output
  • Current input via CT’s 5 Amp, 1 Amp or 333mV
  • Class 1 accuracy
  • IP54 standard
Download data sheet

A Din 96mm single line display, multi display energy meter with dual isolated volt free pulse outputs as standard for KWh & KVArh for interfacing to external equipment such as BMS systems. The CUBE 350 can also be specified optionally with MODBUS RS485 whilst still retaining the pulse outputs, plus an additional harmonics option via MODBUS is also available. The CUBE 350 is suitable for both three phase and single phase loads and if three phase both 3 wire or 4 wire balanced or unbalanced loads, inductive or resistive. The CUBE 350 is fully programmable to set up CT ratios, the CT secondary can be specified at ordering as either conventional 5 Amp or 1 Amp, or as 333mVAC which are used in application scenarios where the CT’s are sited a distance away from the meter and VA burden within the secondary cabling is an issue. The CUBE 350 auto scales to Wh, KWh, MWh etc, depending on the CT ratio programmed. The CUBE 350 is able to accept a very wide voltage input span of 80-480V L-L or 46-277V L-N, thus enabling the CUBE 350 to be used on VT circuits such as 11KV/110V, therefore a VT ratio can also be programmed if required. Optionally an additional Voltage Expander module can be ordered for system voltages from 480-690V L-L / 277-399 L-N +10%

Inputs

System:
1 phase
3 phase, 3 wire or 4 wire balanced or unbalanced

Voltage: 80-480V L-L / 46-277V L-N +0%

Voltage expander:
Optional 480-690V L-L / 277-399V L-N +10%

Current:
Via external 5 Amp secondary CT’s
Measuring range 0.2% to 120%

Frequency: 5-65Hz

Harmonics:
HD to 30th (with Harmonics option)
Individual to 15th (with Harmonics option)

Voltage burden: < 0.1VA per phase

Current burden: < 0.1VA per phase

Voltage overload: x4 for 1 hour

Current overload: x40 for 0.5 Sec max

Auxiliary supply:
230VAC 50/60Hz +15%
On request 110VAC
On request 24VDC

Load:
5
VA max
5W max

General

Temperature: Operating -10 ̊C to +55 ̊C

Humidity: 75% non condensing

Material: Mablex to UL94-V-0, self ext.

Terminals: 4mm rising cage

Dimensions: 96x96x83.5mm (72mm behind panel)

KWh:
Class 1 per EN 62053-21
Class 0.5 per ANSI C12.20

KVArh: Class 2 per EN 62053-23

KW & KVA: Class 0.25 IEC 60688

KVAr: Class 0.5 IEC 60688

Amps & Volts: Class 0.1 IEC 60688

Power Factor: ± 0.2 ̊

Neutral current: Class 0.5 IEC 60688

Pulse outputs:
1 pulse for KWh, 1 pulse for KVArh or KVAh

Scaling: Programmable between 1 & 100 counts of registers

Pulse periods: Programmable between 0.1-20Sec

Type: 2 x NO volt free, optically isolated

Rating: 100mA @ 70VDC/33VAC max

Isolation: 3.5KV for 1 min

TYPE

CUBE 350
CUBE 350 / MODBUS
CUBE 350 / MODBUS / HARMONICS
Dual pulse outputs on all meters as standard

CURRENT INPUT TYPE*

5 Amp
1 Amp
333mV**

OPTIONS*

230VAC aux supply (standard)
110VAC aux supply
24VDC aux supply
Voltage Expander

*Specify
**Please see split core 333mVAC secondary CT’s types: SCL, SCT, ROPE

An optional Voltage Expander is available for the CUBE 350 range for high L-L system voltages between 480V - 690V

CUBE-Voltage-Expander.png#asset:4198

CUBE-350-Dimensions.png#asset:4196