1(4)-20mA DC ADJUSTABLE TRIP AMPS

Product

group

FF

YWRIT, 11WRIT (spco), YWRI2T (2 x spco)

Features

  • Din rail or 11 pin plug in
  • Single setpoint or dual setpoint values
  • Selectable manual or auto reset
  • Low input impedance
  • Dual LED indication
Download data sheet

YWRIT - Din rail 1-20mA adjustable single setpoint trip amp.

11WRIT - 11 pin plug in 1-20mA adjustable single setpoint trip amp.

YWRI2T - Din rail 1-20mA two adjustable setpoints trip amp, 2 x SPCO outputs “Low” & “High”.

YWRIT, 11WRIT

“Auto Reset” without latching mode. This mode is determined by terminals Y1 & Y2 or pins 9 & 11 left open. The output relay is energised when the monitored circuit rises above the level selected via the front potentiometer. The output relay will de-energise when the current falls back below the level selected less the set hysteresis adjustable 5 to 50%, set via a second potentiometer. If the auxiliary supply is lost at any time the relay will also de-energise.

“Manual Reset” latching mode. This mode is determined by a wired link between terminals Y1 & Y2 or pins 9 & 11. The output energises when the monitored circuit rises above the level selected by the front potentiometer. Once energised the relay will remain latched even if the monitored current falls below the set level less any selected hysteresis. Resetting is achieved by opening the link between terminals Y1 & Y2 or pins 9 & 11 or by removing the auxiliary supply. If whilst resetting the monitored current is still above the set level a reset will not be achieved. It is normally preferable in the latching mode to have the adjustable hysteresis set at minimum.

YWRI2T

Two setpoint trip amp. Providing two separately controllable trip levels. With R1 selected as the “High” level and R2 as the “Low” level. When the monitored signal current rises above R2 set level R2 relay will energise. If the current continues to rise above R1 set level, relay R1 will energise. Conversely as the monitored current falls R1 will de-energise, if the fall continues R2 will de-energise. The unit has a built in fixed hysteresis of 2% at each setpoint to avoid relay “chatter”. The YWRI2T does not have a latched option and is therefore “auto” reset on both relays.

Adjustable Time Delays

The trip amps YWRIT & 11WRIT have 3 separately adjustable 0.1-10 sec delays. A start up delay activated by the connection of the auxiliary supply, therefore if a control circuit is going to be permanently live the time delay will only ever be active once. A delay on rising current and a delay on falling. The YWRI2T does not have any time delays.

DC Auxiliary Supply Versions

DC auxiliary supply versions are as standard non isolated. For these versions the supply and the measured current must be isolated from each other and must not exceed 50V DC. On request at extra cost isolated versions can be manufactured utilising internally a DC to DC converter.

Supply & Measuring

Nominal supply tolerance: ±15%

Isolation AC versions: Via transformer

Isolation DC versions:
No as standard
Yes via optional internal DC to DC converter

Power consumption: 3VA max

Hysteresis:
Adjustable 5 to 50% of Ie
YWRI2T fixed at 2%

Repeat accuracy:
±2% at constant ambient
±5% across temperature range

Response time:
100 mSec on make
200mSec on break

Input range: 1-20mA adjustable

Max over current: 1Amp (max 1 sec)

Input impedance: 10 Ohms

Time delays:
0.1-10 secs separately adjustable
YWRI2T no delays

Relay output

Output contacts:
SPCO 10Amps/250V AC1
DPCO 8Amps/250V AC1

Mechanical life: 30 Million ops

Electrical life: 200K ops at max rated load

General

Operating temperature: -20°C to +65°C

Storage temperature: -20°C to +65°C

Max cable size: 4mm

CE marked: Yes

In accordance with:
EN61000-6-1: 2007
EN61000-6-3: 2007
EN61010-1: 2002

Housing material: Polycarbonate, Auto extinguishable to UL 94 V-0

TYPE

YWRIT (din rail SPCO)
11WRIT (11 pin SPCO)
YWRI2T (din rail 2 x SPCO)

COIL VOLTAGE

440VAC
415VAC
400VAC
380VAC
230VAC
110VAC
48VAC
24VAC
*48VDC
*24VDC

* No isolation on DC versions as standard, on request at extra cost isolated versions are available.

YWRIT-Connections-Function.png#asset:3384

Dimensions-YW.png#asset:3270