Product
group
D
Din rail mounted combined phase failure, sequence thermistor relay (Klixon version also available). Available in either 3 or 4 wire and self powered, with separate output contacts and LED indication for phase faults and thermistor faults.
Both contacts energise when all is healthy, the phase relay R2 will de-energise when a phase sequence error is detected or a phase is lost (and in a 4 wire version also the Neutral). The thermistor circuit relay R1 will de-energise on detection of either a short circuit or overheat (resistance below 30 Ohms or above 3.3 KOhms). Both relays are slightly delayed (delay fixed) to avoid nuisance tripping. The LED indicators will diagnose the circuit problems, a healthy situation results in all the LEDs being illuminated.
Supply & Measuring:
Nominal supply:
3 x 110V AC, 3 x 220V AC, 3 x 380V AC,
3 x 400V AC, 3 x 415V AC, 3 x 440V AC
Permanent tolerance: ±15%
System: 3 or 4 wire option
Frequency: 50/60Hz
Nominal Umin (fixed):
80% on all 3 phases
60% on 1 phase drop
Thermistor operating: 3.3 KOhm ±5%
Thermistor reset: 1.8 KOhm ±10%
Max cold resistance: 1500 Ohms
Short circuit detection: 30 Ohms ±20%
Max No. Of PTC sensors: 6
Sensor voltage: 2.5V DC max
Isolation: Via transformer & opto isolator
Max power consumption: <6VA
Insulation: 2.5KV 50Hz impulse
Relay outputs:
Output contacts: SPCO + 1NO 8 Amps/250V AC1
Delay phase sequence: 0.5sec (fixed)
Delay phase loss: 50mSec (fixed)
Delay thermistor fault: 0.5sec (fixed)
Mechanical life: 30 Million ops
Electrical life: 200K ops at max rated load
General:
Operating temperature: -20°C to +65°C
Storage temperature: -20°C to +65°C
Max cable size: 4mm
CE marked: Yes
In accordance with:
EN61000-6-1: 2007
EN61000-6-3: 2007
EN61010-1: 2002
Housing material: Polycarbonate, Auto extinguishable to UL 94 V-0
TYPE
YWRPTC4
KLIXON
*T
VOLTAGE
3 x 110V
3 x 220V
3 x 380V
3 x 400V
3x 415V
3 x 440V**
SYSTEM
3W (3 wire)
4W (4 wire)
OPTION
On 3 wire variants as a no cost option a separate AC auxiliary supply can be specified. This gives the possibility of additonal “control circuit” voltage monitoring. If this is lost or is not present, the unit will de-energise or not energise as applicable. 24VAC, 48VAC, 110VAC
* Insert T if Klixon is required
** 440V only available as a 3 wire version