Product
group
JJ
A range of Din rail mounted Modular voltage supply monitoring relays available in either single phase or three phase configuration and if three phase a choice of 3 wire or 4 wire. Monitoring phase loss and if applicable Neutral loss, along with under voltage.
Single phase units have a nominal supply of 240VAC and three phase units 415VAC. All units are available either with a fixed under voltage trip level or an adjustable trip level. Fixed tripping levels are 170V for single phase units and 300V for three phase units. If adjustable it is on a calibrated voltage scale of 170-250V for a single phase unit and 300-440V for a three phase unit.
On three phase units both 3 wire or 4 wire phase sequence can be specified as an option.
On three phase 4 wire units phase imbalance and Neutral shift can be specified as an option. Phase imbalance is based on voltage amplitude of the phases and is fixed at 15% of imbalance.
All units have an adjustable delay on tripping timer of 0.5-10 secs (not True Delay Off), to ride through short term voltage dips, short term phase loss and if optionally specified phase sequence and phase imbalance errors.
Two LED’s are provided. The green LED illuminates to indicate power is on the unit. The red LED illuminates to indicate the output relay/s is energised. The output relay/s energises when the monitored supply is healthy, that is; all phases and if applicable the Neutral present, if applicable in the correct sequence, the voltage level is within parameters and if applicable within balance.
Standard output contact configuration is SPCO as an option 2NO contacts is available (on request as a special 1NO & 1NC is also possible).
Single Phase units
Nominal voltage: 240VAC L-N
Voltage range: 170-265VAC
Adjustable U/V setpoint: 170-250VAC
Fixed units U/V setpoint: 170VAC
Hysteresis: 2% fixed
Repeat accuracy: <1%
Three Phase units
Nominal voltage: 415VAC L-L
Voltage range: 300-460VAC
Adjustable U/V setpoint: 300-440VAC
Fixed units setpoint: 300VAC
Hysteresis: 2% fixed
Repeat accuracy: <1%
Phase imbalance + Neutral shift option
Neutral shift: Fixed 10% of nominal phase amplitude
Phase imbalance: Fixed 15% of nominal phase amplitude
Note: Only possible on 4 wire units
Relay outputs
Rating: SPCO 8 Amps / 250VAC AC1, 2NO 5 Amps / 250VAC AC1
Special request: 1NO & 1NC
Max switching voltage: 250VAC, 250VDC
Mechanical life: 20 Million ops
Electrical life: 50K ops at max rated load
Isolation voltage: 2KV AC for 1 min
General
Isolation: 2KV for 1 min
Power consumption: < 12VA
Trip delay time: Adjustable 0.5 to 10 secs
Operating temp: -40°C to +65°C
UKCA & CE marked: Yes
Housing material: Polycarbonate, Auto extinguishable to UL 94 V-0
Type
BXP
Configuration & Version
200 Single phase adjustable U/V
210 Single phase fixed U/V
300 3P3W adjustable U/V
310 3P3W fixed U/V
400 3P4W adjustable U/V
410 3P4W fixed U/V
Options
0 No option
1 Phase sequence
2 Phase imbalance + Neutral shift *
3 Phase sequence & phase imbalance + Neutral shift *
4 2NO output contacts
5 2NO output contacts & phase sequence
6 2NO output contacts & phase imbalance + Neutral shift *
7 2NO output contacts, phase sequence & phase imbalance +Neutral shift *
* Phase imbalance + Neutral shift only available on three phase 4 wire units