MIDLAND JAY - SINGLE & THREE PHASE VOLTAGE SUPPLY MONITORING RELAYS FOR HEAVY INDUSTRIAL & ELECTRICALLY NOISY APPLICATIONS FEATURING PHASE IMBALANCE & ASYMMETRY CONTROL

Product

group

JJ

BAE, BAP, BBE, BBP, BCE, BDE, BDP, BMP, BPP, BQE, BQP, BRP, BWP

Features

  • Din rail mounted & surface mounting housings
  • Monitors phase failure & Neutral loss
  • Optional phase sequence detection
  • Optional phase imbalance detection
  • Calibrated voltage scale on adjustable units
  • Single phase & three phase 3 wire or 4 wire units
  • Adjustable time delay on tripping 0.5-30 secs (most True Delay Off)
  • Dual LED indication
Download data sheet

A range of Din rail mounted and surface mounted enclosures, voltage supply monitoring relays for particularly harsh industrial applications and electrically noisy environments.

Construction of most three phase units are based around an internally fitted transformer, not only does this transformer coupled with active filters facilitate a high degree of protection from harmonics and supply irregularities but also enables units to monitor Phase Imbalance and Asymmetry Control as all phases are referenced to the Star point.

These monitoring devices offer protection both from monitoring accuracy and product survival against the following supply phenomenon:-

Harmonic voltage distortion by large non-linear loads such as; soft starts under starting, large variable speed drives and a large number of computers. These effects are exaggerated under weak supply conditions. All product types except for products with prefix BDE are particularly suited for such conditions.

Notching (momentary supply loss / negative transient), caused by large thyristor controlled three phase rectifiers found in DC drives, current source inverters, again the effects are exaggerated under weak supply conditions. Product types with prefix BCE, BMP, BQE, BQP, BAE, BAP, BBP, BWP and BBE are particularly suited for such conditions.

Spikes, caused by switching transients and electrical storms disturbances, supplies in remote locations are particularly prone. Product types with prefix BCE, BMP, BQE and BQP are particularly suited for such conditions.

Single Phase units:

Nominal voltage: 240VAC L-N***

Voltage range: 170-265VAC

Adjustable U/V setpoint: 170-250VAC

Fixed units U/V setpoint: 170VAC

Hysteresis: Adjustable*

Repeat accuracy: < 1%

Three Phase units:

Nominal voltage: 415VAC L-L***

Voltage range: 300-460VAC

Adjustable U/V setpoint: 300-440VAC

Fixed units setpoint: 300VAC

Hysteresis: Adjustable*

Repeat accuracy: < 1%

Phase imbalance:
Adj. 15% of nominal phase amplitude**
Fixed 15%, 25%, 35%, 40% of nominal phase amplitude**

Relay outputs:

Rating: See table

General:

Isolation: 2KV for 1 min

Power consumption: < 12VA

Trip delay time: Adjustable 0.5 to 30 secs

Operating temp: -40°C to +65°C

CE marked: Yes

*Most units, please request individual data sheets for specific details, please call for assistance.

**Depending on exact model type, see ordering information and selection table.

***Other system voltages are available, please call for assistance

BAE-Ordering-table.png#asset:3276

*True Delay Off

Special voltages and frequencies in many of the above products are available on request, please call for assistance.

Individual data sheets specifically on each of the above detailed variations are available, please call for assistance.

BAE-Enclosure-type.png#asset:3277

Recently Viewed Products

Keep Updated

Receive updates about our offers, latests products and more, directly to your inbox