Product
group
GG
Foxtam DC voltage transducers can measure DC voltages directly up to 2000VDC. Specific 0-50mV, 60mV, 75mV are available for use directly with DC current shunts. The transducer converts the input signal to either a DC mA or DC voltage analogue signal output, directly proportional to the input. All DC voltage transducer require an auxiliary supply voltage. The 4KV isolated output signals can be utilised for many applications and can be fed into analogue meters, digital meters, PLC’s or BMS systems.
Transducer types include:-
FOX.TR.DU.U – Uni-polar output for example 4-20mA or 0-10VDC.
FOX.TR.DU.B – Bi-polar transducers which are particularly applicable for applications involving the control of DC motors when reversing polarity to control direction of motion, outputs for example can be -10VDC to 0 to +10VDC or 4-12-20mA.
Accuracy: Class 0.25
Input voltage: 0-20mV...2000V direct
Overload:
1.2 x Un continuous
1.5 x Un for 1 sec
Working range: 0-120% In
Burden: <0.2VA
Case size: 1
TYPE
FOX.TR.DU.U / Uni-polar
FOX.TR.DU.B / Bi-polar
INPUT RANGE
0-50mVDC
0-60mVDC
0-75mVDC
0-20mV....2000VDC*
OUTPUT UNI
0-1mA
0-2.5mA
0-5mA
0-10mA
0-20mA
4-20mA**
0-1VDC
0-5VDC
0-10VDC
OUTPUT BI
+/-1mA
+/-2.5mA
+/-5mA
+/-10mA
+/-20mA
4-12-20mA**
+/-1VDC
+/-5VDC
+/-10VDC
AUX SUPPLY
24VAC
63VAC
110VAC
230VAC
415VAC
24VDC
48VDC
110VDC
*Specify exact voltage input, above 600VDC a price surcharge is applicable.
**Also possible on bi-polar units to have as an example 0-5-10VDC output.