Product
group
DD
Din 48x24mm 4 digit microprocessor based digital panel meters, available with a wide choice of both AC and DC voltage or current inputs including standard and non standard analogue signal inputs. PT100 & PT1000 temperature inputs can also be specified. The meters are can be programmed by four tactile switches that can be specified to be accessed directly on the front panel or specified as discrete, where the buttons are hidden behind the front screen. These meters are display only meters and have no outputs, for meters Din 48x24mm with outputs please see meter type CS3.
Programming & set up buttons can be specified with “Visible Buttons” on the front panel or “Discrete Buttons” behind the front screen. If not specified, meter will be supplied with “Discrete Buttons”
The following functions can be set up at the time of ordering, or programmed if required at a later date:
AvG to increase or decrease the response time, factory default 100mSec
dF iLT to increase filtering on noisy supplies possibly to be utilised in conjunction with AvG.
LoCUt to ignore induced readings at zero from leaky circuits or noise pick up, but not at the detriment of a real reading. For example if LoCUt value of 5 set, any reading of 5 or below is ignored, but when reading is genuinely say 100 the meter reads 100 and not 95.
AoLS low scale point when scaling say to other engineering values, can be set from -1999 to +9999 the meter has the facility to also fine adjust.
AoHS high scale point when scaling say to other engineering values, can be set from -1999 to +9999 the meter has the facility to also fine adjust
Further details and assistance on the above set up features are available from our sales office.
Measuring accuracy (VAD):< +0.1% FS + 1 digit
Measuring accuracy (VAA):< +0.2% FS + 1 digit
Measuring accuracy (VAAT): < +0.2% FS + 1 digit
Measuring accuracy (TR): < +0.1% FS + 1 digit
Temperature effect: < 100 PPM/ºC
Sampling rate: 15 cycles / sec
Response time: < 100mSec (standard) Can be altered in set up
Display: 4 x red LED’s
Display range: -1999 to +9999
Decimal point: At any point or not at all
Maximum over range:
Voltage x1.2 rated voltage continuous
Current x1.2 rated current continuous
Aux Supply:
5VDC (4.5-9VDC)
12VDC (9-18VDC)
24VDC (18-36VDC)
48VDC (36-72VDC)
ADH 85-264VAC & 100-300VDC
Power consumption:
AC: <1.5VA
DC: <1W
Operating temperature: 0-60ºC
Operating humidity: 20-95% RH
Dielectric strength: 2KV for 1 min, between input & aux.
Insulation resistance: > 100MOhms @ 500VDC between input & aux
EMC: EN55011:2002 & EN 61326:2003
Low voltage directive: EN61010-1:2010
Dimensions mm: 48(W) x 24(H) x 78(D)
Panel cut out mm: 45(W) x 22.5(H)
Case material: ABS (UL 94V-0)
Terminals: Screw max 2mm²
The meter will be scaled exactly to your requirements, please specify any special scaling required and any scaling to other engineering units.
Please also specify if front programming / set up buttons are to be “Visible” or “Discrete”.
Receive updates about our offers, latests products and more, directly to your inbox